How to set a switchgear's ratings
Give a switchgear its bus rating and interrupting rating so EVpin can check it against the main breaker and fault current.
By the end your switchgear will have a bus rating and an AIC rating, and the panel schedule will check both. You need a design with a switchgear between the transformer and the power cabinet, as in How to add a switchgear, and electrical design turned on.
Click a bus rating
Click a bus rating at or above the recommended main breaker on the Panel Schedule tab. This design needs a 600 A main, so it uses an 800 A bus.

Click an AIC rating
Click an interrupting rating at or above the fault current the utility quotes for the service. Without a quote, EVpin estimates it from the transformer, about 10.5 kA here, so the design uses 22 kAIC.

What's next
- How to change a switchgear's size to match the gear you plan to install.
- How to see a design's panel schedule for the main breaker the bus is checked against.